⚫ Voltage class: | 15KV |
⚫ Max.Rating Phase to Phase: | 14.4 kV |
⚫ Max.Rating Phase to Ground | 8.3kV |
⚫ AC 1 Minute Withstand: | 34 kV |
⚫ DC 15 Minute Withstand: | 53 kV, ≤10 pC |
⚫ BIL and Full Wave Crest: | 95 kV |
⚫ Minimum Corona Voltage Level: | 11kV |
⚫ Continuous: | 200 amps rms |
⚫ Switching: | 10 Operations at 200amps rms at 14.4kV |
Winding Wire’s Loadbreak Elbow Connectors are engineered for use in medium-voltage underground distribution systems, offering a secure, flexible, and fully shielded separable connection. These connectors allow for loadbreak switching, meaning they can be safely connected or disconnected under load conditions, making them ideal for pad-mounted switchgear, transformers, and junctions.
Manufactured with high-quality EPDM insulation and precision-molded components, our loadbreak elbow connectors are tested to exceed IEEE 386 and ANSI/IEEE C119 standards, ensuring performance under a wide range of environmental and electrical stresses.
With a robust design and dependable performance, Winding Wire’s Loadbreak Elbow Connectors offer a safe and efficient solution for modern medium-voltage distribution systems.