⚫ Voltage class: | 15KV |
⚫ Max.Rating Phase to Phase: | 14.4 kV |
⚫ Max.Rating Phase to Ground | 8.3kV |
⚫ AC 1 Minute Withstand: | 34 kV |
⚫ DC 15 Minute Withstand: | 53 kV, ≤10 pC |
⚫ BIL and Full Wave Crest: | 95 kV |
⚫ Minimum Corona Voltage Level: | 11kV |
⚫ Continuous: | 200 amps rms |
⚫ Switching: | 10 Operations at 200amps rms at 14.4kV |
Our 15kV 200A Bushing Insert is a key component for connecting load-break elbow connectors to universal bushing wells in medium-voltage underground power distribution systems. Engineered to meet the requirements of IEEE Std 386, this insert transforms a standard bushing well into a fully functional loadbreak interface, allowing for safe and efficient live connection and disconnection under load.
Constructed using high-quality peroxide-cured EPDM rubber insulation and corrosion-resistant copper alloy contacts, the bushing insert ensures superior electrical performance, mechanical strength, and environmental durability. Its compact, dead-front design enhances operator safety and system reliability in pad-mounted transformers, switchgear, and other medium-voltage applications.
Our 15kV 200A Bushing Insert is your dependable solution for secure and flexible terminations in medium-voltage distribution networks. Built to perform in the most demanding utility environments.